Product Overview: An electronic power meter that measures voltage, current, and frequency across three-phase systems, supporting both wye and delta configurations at 120/208VAC. It features a keypad display interface, diagnostic mode, NVRAM-based settings, and communication capability for monitoring electrical power distribution in industrial and utility applications.
Category: Control Assembly
Manufacturer: General Electric
Manufacturer Synonyms: GE
Manufacturer Part Number: 3720 ACM
Common Failures
Typical issues with this product include power-up failures, incorrect voltage display, and communication problems. These symptoms often result from faulty capacitors, memory issues, or oxidation on circuit boards.
Repair Approach
Repairs may involve replacing defective capacitors, reprogramming memory components, and cleaning oxidation from circuit boards. In cases of incorrect voltage display or communication issues, Non-Volatile Random Access Memory (NVRAM) may be copied and flashed to a new unit, and timekeeping RAM may be replaced. Thorough board inspections and cleaning are performed where insects or liquid damage is detected.
Testing & Quality
Post-repair testing confirms the restoration of functionality. This includes verification of DC voltages and the correct operation of all buttons and display components. Units are also checked to ensure they measure voltage and frequency accurately. Diagnostic modes are accessed to confirm no errors are present, and final testing is conducted to ensure customer settings and software are operational.
Service and repair your broken General Electric part
We can repair your General Electric model 3720 ACM in our facility. Let our skilled technicians get your General Electric back in operation quickly.
Step 1 - Click the green 'Repair Now' button above to add the part and then complete the RMA.
Step 2 - The RMA form will be sent to you via email. Print the RMA form and put it in a box with the item(s) for repair.
Step 3 - Ship or mail the box to the address listed on the RMA.
Once the user has seen at least one product this snippet will be visible.