Common Failures
A frequently observed issue with this product is a display problem, where it shows a random pattern after startup. This has been associated with component degradation.
Repair Approach
In cases where weak electrolytic capacitors were identified during evaluation, the corrective action involved replacing the affected electrolytic capacitors to restore proper function. This repair typically required approximately 5 hours of bench time.
Testing & Quality
Following repair, the product underwent thorough testing, which included standard functional tests and a burn-in process. Verification was also performed for S-type thermocouple functionality where applicable.
Service and repair your broken Nabertherm part
We can repair your Nabertherm model TL6 in our facility. Let our skilled technicians get your Nabertherm back in operation quickly.