Common Failures
One frequently reported issue is the equipment tripping the breaker after the gearmotor is replaced. The failure is often intermittent and difficult to verify. A primary cause identified is the electrolytic capacitors being out of specification, with some capacitors failing open or losing capacity over time.
Repair Approach
In cases where capacitors are found to be out of specification, they are replaced. Typically, a comprehensive clean-up of the drive is performed as part of the repair process.
Testing & Quality
After completing repairs, the device undergoes testing, including powering up and verifying operational functionality. A burn-in test lasting one hour is conducted.